R422D

CertiFlow is a record system for refrigerants, and works with a GWP of 2729 for R422D — the value fixed on every booking.

R422D (mengsel)

The numbers

GWP (AR4, 100-year)

2,729

Family

HFC

Blend

Safety class

A1

Status

Restricted for servicing

Use for servicing existing equipment is restricted; recharging is subject to conditions.

From kilograms to obligation

What a given charge means for the CO₂ equivalent and for the check interval.

ChargeCO₂ equivalentLeak check
1.83 kg4.994 tThis charge stays below the 5 t CO₂-eq threshold. No periodic leak check is required.
2 kg5.458 tAt least every 12 months
18.32 kg49.995 tAt least every 12 months
25 kg68.225 tAt least every 6 months
183.22 kg500.007 tAt least every 3 months

Last checked: 2026-08-09 · F-gas regulation